As a heat pump from standard production, the Vitocal 350-HT Pro high temperature heat pump delivers flow temperatures up to 90 °C and utilises heat source temperatures up to 45 °C. This makes it particularly suitable for the utilisation of waste heat and for the generation of high temperatures for industrial and commercial processes, or for older district heating networks.
Large heat pump
High temperature brine/water heat pump with the option of water/water operation with intermediate brine circuit.
Rated heating output for brine/water operation
56.6 to 144.9 kW (B0/W35)
Rated heating output for water/water operation
133.3 to 351.5 kW (W45/W90)
Maximum flow temperature up to 90 °C
Specially designed for the utilisation of waste heat in renewable heat for the commercial sector
Low running costs with maximum efficiency
Through innovative refrigerant cycle diagnostic system with electronic expansion valve
Remote monitoring and communication
Through numerous data communication options
Optimum utilisation of waste heat
Due to high permissible primary source temperature of up to 45 °C
Low sound power
< 66 dB (A)
Intuitive operation of the PLC control unit
Via touchscreen and schematic diagrams
10 bar pressure rating
For industrial applications
Low service costs
Through automatic leakage monitoring
Easy commissioning
Through menu-guided assistant functions
Factory test at operating temperature
With function and performance tests
Vitocal 350-HT: high temperature heat pump for utilisation of waste heat in renewable heat for the commercial sector
The use of renewable heat in commercial applications is determined by the need for high flow temperatures.
In addition, the control unit features many communication options. LAN-supported systems as well as Modbus and BACnet interfaces can be used. These make the system accessible for remote monitoring and integration into building management systems. The 5.7 inch colour touchscreen offers intuitive operation and easy control.
Product details
- Rated heating output (kW), to EN 14511, B0/W35, spread 5 K
-
Type BW 353.AHT058: 56.6 kW | type BW 353.AHT071: 72.4 kW | type BW 353.AHT084: 83.2 kW | type BW 353.AHT096: 96.6 kW | type BW 353.AHT119: 116.8 kW | type BW 353.AHT126: 124.8 kW | type BW 353.AHT147: 144.9 kW
- Rated heating output (kW), to EN 14511, W45/W90, spread 10 K
-
Type BW 353.AHT058: 133.3 kW | type BW 353.AHT071: 174.7 kW | type BW 353.AHT084: 202.2 kW | type BW 353.AHT096: 234.4 kW | type BW 353.AHT119: 262.8 kW | type BW 353.AHT126: 303.3 kW | type BW 353.AHT147: 351.5 kW
- Coefficient of performance ε (COP) B0/W35
-
Type BW 353.AHT058: 4.3 | type BW 353.AHT071: 4.3 | type BW 353.AHT084: 4.2 | type BW 353.AHT096: 4.2 | type BW 353.AHT119: 4.1 | type BW 353.AHT126: 4.2 | type BW 353.AHT147: 4.2
- Coefficient of performance ε (COP) for water/water operation with intermediate brine circuit W10/W35
-
Type BW 353.AHT058: 3.2 | type BW 353.AHT071: 3.2 | type BW 353.AHT084: 3.2 | type BW 353.AHT096: 3.2 | type BW 353.AHT119: 3.2 | type BW 353.AHT126: 3.2 | type BW 353.AHT147: 3.2
- Application area
-
Commercial enterprises, industrial applications, local authority premises, modernisation projects, new build
- Operation
-
Vitotronic 200 PLC 2.0 control unit with large colour touchscreen
- Product cross-section
-